Pile Bearing Capacity from SPT

Enter the pile — type, section, size and length —, the soil layers and the N values of an SPT boring to estimate the bearing capacity and allowable load by Aoki-Velloso's and Décourt-Quaresma's methods.

Charts

Pile

Type
Section

Tip area Ap = 0.1257 m², perimeter U = 1.257 m. The pile's head is at the surface.

Layers

  1. m
  2. m
  3. m

From the top down, each layer with its soil in Aoki and Velloso's classification and the depth of its bottom. They must reach the tip.

SPT boring

Depth (m)NSPT

One N per test, usually every meter. They must reach the tip; the one just below it counts in Décourt-Quaresma's tip.

Design

Pa = R/FS; NBR 6122 asks for FS = 2 with semi-empirical methods. Allowable loads below P are marked.

  • Each N stands for the stretch between its test and the one above (the first from the surface); the pile's head is at the surface, and its tip takes the N of the stretch it's in.
  • Aoki-Velloso: rp = K·Np/F1 and rl = α·K·N/F2, with K and α from each stretch's soil (Aoki and Velloso, 1975) and F1 and F2 from the pile type (Cintra and Aoki, 2010).
  • Décourt-Quaresma: rp = α·C·Np, Np being the mean of the N at the tip and just above and below it; rl = β·10(Nl/3 + 1), Nl being the mean along the shaft without the N used at the tip, each between 3 and 50. α and β from Décourt (1996) for bored, CFA and root piles; 1 for driven ones.
  • N above 50 is taken as 50. The allowable load is R/FS (NBR 6122 asks for FS = 2 with semi-empirical methods); in bored piles, the tip carries at most 20% of it.
  • The length chart puts the tip at each test's depth, with the same pile and profile.
  • The 3D is an illustration: the bars over the head of cast-in-place piles (φ16) and the Franki pile's base show the work as built but aren't designed here, and the base isn't counted in the capacity.